D1 is a Industrial Rogowski coil integrator installation in distribution box,in a plastic 1 module DIN-RAIL enclosure, powered directly from the mains.
D1 can be combined with any model and size of Y-FCT or FCT Rogowski coils.
The available values are: 0-5VDC,0-5VAC,4-20mAC.
On request the input value can be customized according to the application.
D1 and Rogowski coil is a very flexible system, suitable for high power load analysis, impulsive current monitoring, DC ripple measurement, etc.
Due to its specific features, flexible Rogowski coil is an extremely comfortable solution for current measurement and can be used in a number of cases where traditional current transducer is not the adequate solution.
Specification:
Model | D1.1 | D1.2 | D1.3 |
Rated output | 5V AC rms | 5V DC(true-rms) | 4-20mA |
Maximum Output(overload) | 10V AC rms | 5V DC | 25mA |
Output Ripple factor | 0.5% | Default 5% (relay to Response time) | |
Response time | ≤1us | Default 100ms(adjustable) | |
Power consumption | 150mW | 200mW | |
Bandwidth | 10Hz to 20kHz | 20-2kHz | |
Rated Input | 100A 600A 1000A 3000A 6000A | ||
Read Accuracy | 0.5% typical at 1%(≥10A) to 200% of rated Current @25℃ | ||
Phase error | ≤0.5° | ||
Linearity | ±0.2% of reading(1% to 200% of range) | ||
Minimum Current measurement | 1A (Ripple 100mA) | ||
Output on 0A (zero drift) | ≤2mV | ||
Temperature drift | 200ppm/℃ | ||
Weight | 60g | ||
Dimension | 90*61*18mm | ||
Power supply | 12V or 24V(best performance on 24V default) | ||
Operating temperature | -20℃ to 70℃ | ||
Storage temperature | -30℃ to 90℃ | ||
Relative humidity: | 80% max.without condensation | ||
Protection degree: | IP20 | ||