Rogowski Coil with Integrator Kit for Oscilloscope
model: VPI-FI-333mv
Type: Flexible Rogowski coil current transformer supplied with conditioning circuit
Accuracy: ±1.0% of reading from 5% to 120% of rated current
Conductor Position Sensitivity: ±1.5% at edge Phase Angle: ±0.50 degrees (30 minutes) from 5% to 120% of rated current
Frequency: 50/60 Hz nominal, (safe to operate at any frequency)
Maximum Voltage: 600 Vac
Maximum Over Range Current: 10,000 amps
Safety Standards: CAT III, 600 Vac
UL standard 61010B-1
Conditioning Circuit Output: 0.333 Vac at rated current
Output Wires: 8 feet (2.4 m), 22 AWG, white /black twisted pair
Coil Lead Length: 8 feet (2.4m)
Power Requirements: 10-30 Vdc (12 Vdc or 24 Vdc recommended) 50 mA typical, 70 mA maximum