Product description:
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35 / 7.5 or 15
Built in DC OK active signal
LED indicator for power on
No load power consumption<0.75W
100% full load burn-in test100% full load burn-in test
Common size:
OUTPUT | ||||
Model | MDR-10-5 | MDR-10-12 | MDR-10-15 | MDR-10-24 |
DC Voltage | 5V | 12V | 15V | 24V |
Rated Current | 2A | 0.84A | 0.67A | 0.42A |
Current Range | 0-2A | 0-0.84A | 0-0.67A | 0-0.42A |
Rated Power | 10W | 10W | 10W | 10W |
Ripple & Noise | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p |
Voltage Adj. Range | -5%,+10% | ±10% | ±10% | ±10% |
Voltage Tolerance | ±2% | ±1% | ±1% | ±1% |
Setup, Rise, Hold Up Time | 1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full | |||
INPUT | ||||
Voltage Range | 85 ~ 264VAC 120 ~ 370VDC | |||
AC Current | 0.88A/115VAC 0.48A/230VAC | |||
Efficiency | 74% | 84% | 83.5% | 85% |
Inrush Current | COLD START 35A/115VAC 65A/230VAC | |||
PROTECTION | ||||
Over Load | 105%~160% | |||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
Over Voltage | 115%~135% | |||
Protection type: Shut down o/p voltage, re-power on to recover | ||||
ENVIRONMENT | ||||
Working Temp., Humidity | -10°C~+60°C; 20%~90%RH | |||
Storage Temp., Humidity | -40°C~+85°C; 10%~95%RH | |||
Temp. Coefficient | ±0.03%/°C(0~50°C) | |||
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes | |||
SAFETY | ||||
Withstand Voltage | I/P-O/P: 3KVAC | |||
Isolation Resistance | I/P-O/P: 100M Ohms / 500VDC | |||
STANDARD | ||||
Safety Standard | Design refer to UL60950-1,TUV EN60950-1,EN50178 | |||
EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3 | |||
OTHERS | ||||
Dimension | 25*93*56mm(L*W*H) | |||
Weight | 0.15Kg | |||
Packing | 100pcs/carton | |||
NOTE | ||||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |